Related Links:
Asbestos-Lead-Mold
Building Coordinators
Building Coordinators
Handbook
Contractor Safety
Confined Spaces
Emergency Shelter List
Pesticides PCB's
Pollution Prevention
Resource Conservation
and Recovery Act
Safety
Compliance IGP 156
Safety Manual
Safety Training
Safety Links |
Safety Manual Chapter 5
Fire Regulations - Issue Date
5/75
5-1 Responsibilities
The management of heat generating sources is the responsibility of the department heads and/or Chairperson. Heat generating sources, which include flames, candles, halogen lamps, torch lamps, space heaters, and any other heat sources, are prohibited in Campus Facilities and Residence Halls. If any heat generating source mentioned above appears to have been used, (e.g. a candle with burnt wick), the heat source must be removed from the building.
Heat sources which include flames may be use in a laboratory design for the using heating sources. The classroom setting does not qualify as a laboratory. For maintenance work and other operational needs contact the Environmental Health and Safety Department for a "Hot work permit".
5-2 Procedures For Reporting A Fire
- 5-2.01 Procedures are as follows: An alarm
is received at the E-911 Coles County Emergency Communication
(CCEC),
(Possible addendum - A predetermined identification code
to be given preceding the actual reporting of the fire alarm.
This will identify the caller as being legitimate.)
- 5-2.02 The fire alarm monitoring console located in the
E-911 CCEC provides constant monitoring by the CCEC personnel
on all systems with the exception of Burl Ives Art Studio,
Greek Court, University Court, McAfee, Booth House, Buzzard
House, and some other small buildings.
- 5-2.03 These buildings have a local protection system and
alarms sound only within the building. When an alarm sounds,
this alarm must be acknowledged by phone to the E-911.
- 5-2.04 When an alarm is indicated on the fire alarm monitoring
console in E-911 CCEC, this alarm is relayed to the City Fire
Department and the University Police by phone .
- 5-2.05 All fires shall be reported by pulling the pull station
alerting all occupants to leave the building.
To report a fire in a building not equipped with an automatic
fire alarm system, you must dial 911.
- 5-2.1 General Alarm Condition
- 5-2.11 On discovery of a fire, smell of smoke, or suspicion
of a fire, the person or persons shall immediately go to the
nearest pull alarm and activate.
- 5-2.12 All fire alarms shall be treated as a fire condition
and the Building Coordinator will make an attempt to immediately
initiate the fire evacuation policy.
- 5-2.13 When a general alarm is received by E-911, the communication
operator shall follow the steps of procedure as outlined immediately
below:
- 5-2.131 Call the City Fire Department giving any information
available.
- 5-2.132 Dispatch UPD Officer to check on alarm condition.
If a fire is in process, the officer will notify Vice President
of Student Affairs (VPSA) and Vice President of Business Affairs
(VPBA) to activate the Emergency Management Team.
- 5-2.133 Notify the shift electrician.
- 5-2.2 Facilities With No Alarm System
- 5-2.21 Person or persons shall call E-911 and give details
to communications operator.
- 5-2.22 Communications operator shall use reporting procedures
as stated in 5-2.131 through 5-2.133.
- 5-2.3 Fire Reports
- 5-2.31 Fire reports shall be made by the UPD Officer with
copies forwarded to the appropriate departments. (Appendix
II)
5-3 Residence Halls
- 5-3.1 Fire Exit Drills
- 5-3.11 The purpose of fire exit drills is to ensure the
efficient and safe use of the exit facilities available. Proper
drills ensure orderly exit under control and prevent panic.
- 5-3.12 Fire exit drills shall be held once each semester
and within the early part of each semester.
- 5-3.13 False alarms and/or actual fire conditions shall
not be concluded to be a substitute for a fire exit drill.
- 5-3.2 Fire Drill Procedures
- 5-3.21 Housing Office shall submit the fire exit drill schedule
desired for each residence hall to the Safety Officer.
- 5-3.22 Drills shall be held at unexpected and unannounced
times, under varying conditions to simulate the unusual conditions
obtained in case of a fire.
- 5-3.23 Drills shall include suitable procedures to make
sure that all persons in the building, or all persons subject
to the drill follow evacuation plans.
- 5-3.3 Supervision of Drills
All drills shall be attended and reviewed by the Safety Officer,
Fire Department, and Building Coordinator.
- 5-3.4 Reporting
- 5-3.41 A fire exit drill report shall be filed with the
Safety Officer, UPD Office, and Housing Office prepared by
the Building Coordinator. (Appendix II)
- 5-3.5 Evacuation
- 5-3.51 Housing Office shall develop an evacuation plan in
relation to their specific physical facilities and review
once every year prior to fall semester.
Section 5-3 5-3.5 Evacuation (cont.) 5-3.511 Such plans shall
be submitted in writing to the Safety Officer for review and
contain the following information:
- 5-3.512 Floor plans of building indicating evacuation procedures
and number of people using each stairway and exterior doors.
- 5-3.513 Indicate assembly area or areas outside of building
facilities.
- 5-3.52 Evacuation shall be mandatory and no one permitted
back inside the building until the City Fire Department or
Safety Officer has concluded the building is safe to enter.
- 5-3.6 Fire Captains
- 5-3.61 Building Coordinators shall appoint fire captains
for each floor of each residence hall.
- 5-3.62 Fire Captains, upon hearing an alarm, shall immediately
supervise the complete evacuation of the floor under their
jurisdiction.
- 5-3.63 When all residents have evacuated the floor, fire
captains shall check to make sure all corridor windows are
closed, then check the fire doors at the stairway exits to
see if they are closed, proceeding to exit the building.
- 5-3.64 Fire captains will report to the assembly area and
notify the Building Coordinators of any problems on the respective
floor area of responsibility, or that said area has been completely
evacuated.
- 5-3.65 Building Coordinators and Fire Captains shall be
required to attend a fire safety and training program at the
beginning of each semester.
5-4 Fire Safety Inspections
- 5-4.1 The conduct of systematic inspections to locate and
eliminate fire hazards in an indispensable element of the
Fire and Safety program.
- 5-4.2 The Safety Officer will cause regular inspections
of all facilities at least once annually.
- 5-4.3 Residence halls and places of public assembly shall
be inspected more often, as deemed necessary.
- 5-4.4 Agencies other than the Safety Office that may be
utilized are: State Fire Marshal, Charleston Fire Department,
and the University's property insurance carrier.
- 5-4.5 Reports of all inspections shall be forwarded to the
building fire and safety representatives and appropriate vice
presidents, if corrective action is necessary.
- 5-4.6 Spot re inspection shall follow to assure compliance
of the inspection.
5-5 Portable Fire Fighting Equipment
- 5-5.01 Portable extinguishers are intended as a first line
of defense to cope with fires of limited size. Only qualified
persons who have been properly trained in their use should
attempt such operations. Knowing their limitations is the
basic element of such a fire defense.
- 5-5.02 Fire extinguishers and cabinets are marked according
to the classification and these are to be used only on classes
of fire so indicated. (See 5-5.05)
- 5-5.03 Maintenance and charging between annual inspection
shall be performed by the University's contractor. Coordination
of this service is done by Environmental Control [Ext. 2178].
For pick-up and delivery for such service, call Work Control
at EXT. 3416.
- 5-5.04 Training in the proper use of fire extinguishers
shall be an on-going program in cooperation with the City
Fire Department, the Coles County ESDA, and the City of Charleston
ESDA.
- 5-5.05 Fire Extinguisher Classification
Ordinary Combustibles - An extinguisher bearing this symbol
can be used on paper, cloth, wood, upholstery, and other
ordinary combustibles.
Flammable Liquids - An extinguisher bearing this symbol
can be used on gasoline, oil, grease, and other flammable
liquids.
Electrical Equipment -
An extinguisher bearing this symbol
can be used on live electrical equipment.
Combustible Metals -
An extinguisher bearing this symbol
can be used on combustible metals.
- 5-5.1 Inspection, Maintenance and Recharging
- 5-5.11 Inspection
- 5-5.111 Extinguishers shall be inspected monthly if applicable,
or at more frequent intervals when circumstances require.
- 5-5.112 The extinguisher shall be in its designated location.
- 5-5.113 Access to, or visibility of, the extinguisher shall
not be obstructed.
- 5-5.114 The operating instructions on the extinguisher name
plate shall be legible and face outward.
- 5-5.115 Any seals or tamper indicators that are broken or
missing shall be replaced.
- 5-5.116 For water type extinguishers, their fullness shall
be determined by "hefting".
- 5-5.117 Any obvious physical damage, corrosion, leakage,
or clogged nozzles shall be immediately reported to the Safety
Officer or Environmental Control.
- 5-5.118 Pressure gauge readings when not in the operable
range, shall be recharged immediately. Call Environmental
Control Ext. 2178.
- 5-5.119 Record Keeping -- A master list of all fire equipment
is kept at Environmental Control.
- 5-5.1191 Building Fire and Safety Representative shall inspect
all fire extinguishers each month and make a report of the
inspection. (Appendix VI)
- 5-5.1192 The date of the inspection was performed and the
initials of the person performing the inspection shall be
recorded on the tag of the extinguisher.
- 5-5.12 Maintenance and Recharging
- 5-5.121 Maintenance and Recharging shall be accomplished
by the Environmental Control and/or a licensed agent.
- 5-5.122 All portable extinguishers shall have a maintenance
check not more than one year apart or when indicated by inspection
by Environmental Control and/or a licensed agent.
- 5-5.122 All portable extinguishers shall have a maintenance
check not more than one year apart or as necessary from indications
after inspection.
- 5-5.123 Extinguishers out of service for maintenance or
recharging shall be replaced by spare extinguishers having
same classification or equal rating.
- 5-5.124 All extinguishers shall be recharged after use or
as indicated by inspection or according to frequency as required
by the manufacturer and/or NFPA Pamphlet 10.
- 5-5.125 Tags shall be attached to extinguishers showing
yearly inspection dates.
- 5-5.126 Labels shall be attached to indicate date and year
of all hydrostatic tests.
5-6 Inspection and Testing Fire Alarm Systems
Annual Service Tag Monthly Inspection This tag denotes date
of (Reverse Side) service performed by, initials and service
censed agent annually. Maintenance record by building Fire
and Safety Representative/ Environmental Control if applicable.
Hydrostatic Test Label Attached to extinguisher indicating
date of hydrostatic test.
5-7 Inspection and Testing of Sprinkler System and Fire Suppression
Systems
- 5-7.1 The responsibility for properly maintaining a sprinkler
system is the obligation of the owners of the property.
- 5-7.12 Automatic sprinkler systems installed in accordance
with NFPA standards require a minimum of inspection, testing,
and maintenance; however, deterioration or impairment may
result from neglect. Definite provision for periodic competent
attention is a prime requirement if the system is to serve
its purpose effectively.
- 5-7.13 A competent and reliable employee should be given
the responsibility of regularly inspecting, testing, and maintaining
the system and reporting any troubles or defects to his/her
supervisor who should immediately contact the Campus Safety
Officer. This employee should have proper instruction and
training and a general understanding of the mechanical requirements
of operation Inspection And Testing of Standpipe Systems.
5-8 Inspection and Testing of Standpipe Systems
- All valves should be operated prior to testing to assure
proper operation.
- All outlet valves should be closed with caps removed to
check for leaking valves under pressure.
- Connect cap gauge to ground floor system outlet . open
valve.
- Connect Hydrant gate valve to Fire Department Connection
then hose line to fire truck.
- Make arrangements necessary to protect building from water
damage at top of building such as attaching 1.5 in. hose at
top outlet to carry water away from building.
- Pump water into system at low pressure removing air from
top outlets. Close outlet valve when full.
- When system is full of water close Hydrant gate valve down
that it is slightly open (one turn open).
- Slowly increase pressure to desired test pressure.
- Close hydrant gate valve when desired pressure is obtained.
System should not leak off. Check cap gauge on system outlet
first floor.
- During test all piping should be inspected for leaks.
- Complete test by draining system, opening P.I.V. valves,
and replacing outlet caps and valve seals.
- Place systems in service.
Calculated pressures needed to meet N.F.P.A. requirements.
NFPA 25 3-3.2.1 Indicated that a Hydrostatic tests at not
less than 200 psi pressure for 2 hours, or at 50 psi in excess
of the maximum pressure. where maximum pressure is in excess
of 150 psi, shall be conducted every 5 years on dry standpipe
systems and dry portions of wet standpipe systems.
NFPA 25 3-3.2.3 The hydrostatic tests shall be measured at
the low elevation point of the individual system or zone being
tested. The inside standpipe piping shall show no leakage.
EIU's test methods are to hydrostatic test the standpipe
system at 135 psi at the highest hose connection on the system
in accordance with NFPA 25 3-2.2.1 and NFPA 25 3-3.2.3.
5-9 Fire Reports
- 5-9.01 Fire reports (Appendix II & IV) are of a vital
necessity in any fire safety program. Not only will such reports
indicate the extent of damage and dollar loss, but will also
reveal fire prevention techniques which can be implemented.
- 5-9.02 Experience has shown that the first people on the
fire scene can give much information in helping to determine
the cause and origin of fires. Fire reports reflect such information
from different sources, being the basic tools of determination.
- 5-9.03 Section Six (6) Ten (10) and Sixteen (16) of the
Fire Marshal Act, State of Illinois requires that such determinations
and reports be filed.
- 5-9.04 All fires, regardless of how minor or if burned out
prior to discovery, shall be reported to the Safety Officer.
- 5-9.05 It is the duty of the Safety Officer to determine
the cause and origin of all fires with the cooperation of
all departments and personal.
- 5-9.1 All fires, regardless of how minor or if burned out
prior to discovery, shall be reported to the Safety Officer.
- 5-9.2 All fire alarms, either false, malfunction in system,
or to indicate a fire shall be reported to the Safety Officer.
- 5-9.3 It shall be the responsibility of the building fire
and safety representative to file such reports.
- 5-9.4 University Police Department shall file such reports
indicated in 5-9.1 and 5-9.2 above.
- 5-9.5 The responding Police officer shall make reports in
such responses, with copy being filed with the Safety Officer.
- 5-9.6 Determining cause and origin of all fires shall be
the responsibility of the Safety Officer and City Fire Dept.
- 5-9.7 It shall be the responsibility of the responding UPD
and/or Safety Officer to secure the fire scene.
- 5-9.8 No one shall be permitted to enter or remove any articles
from the fire scene. Clean-up operations shall begin only
after the proper authorization from the Safety Officer.
- 5-9.9 When all reports are filed, the Safety Officer shall
compile a final report and forward to designated persons.
- 5-9.10 All reports are to contain as much information as
requested on the reports as well as other vital data to determine
cause and origin.
- 5-9.11 Fire report (Appendix IV) form is to be used in reporting
actual fires only.
- 5-9.12 Fire & Safety Exit Drill Report form (Appendix
II) shall be used to report all other alarm conditions.
5-10 Theaters and Stage Facilities
- 5-10.1 Inspection and testing of all fire suppressions systems,
such as halon and other systems, shall be performed at least
annually by qualified contractors.
- 5-10.2 It shall be the responsibility of the department
in which the fire suppression system is located to ensure
that the annual inspecting and testing is performed and to
send a copy of the results to the Campus Safety Officer.
5-11 Hot work-- Cutting, Welding and Heat Sources
Hot work permits.
-
Definitions:
Hot work is the process of using torches, welders or any other heat or sparking equipment to perform construction and maintenance activities.
Hot Work Permit is a system to manage the risk of having an open flame or heat sources present in a building. The Hot Work Permit program's objective is to notify departments and personnel that an unusual hazard is about to be conducted and special precautions should be taken.
5-11.2 Notifications will need to be given to the Facility Planning and Management's Electric shop and Work Control to notify the building's coordinator. Upon notification they will disable the building's central fire alarm. It is very important to release the area upon completion of the work so the fire alarm system is operational for balance of the day.
5-11.3 The Electric shop will notify the CCOM 911 that the building's fire alarm and smoke detector system is out of service for the reason for the interruption. Work Control shall give notification to the Building's Building Coordinator.
5-11.4 The FPM or contractor's employees shall clear away all combustibles and cover any combustible materials that cannot be relocated. After the site preparation is completed then the Hot Work may be started. A second employee should be present to monitor the work and recognize when welding sparks or any other hot materials are landing in an area where a fire may be started. Fire watch personnel are authorized to stop work when a fire hazard condition exists. The fire watch activity shall be continued for 30 minuets after the Hot Work has been completed. FPM's Electric shop must be notified that Hot Work has been completed before the person on fire watch maybe released
5-11.5 FPM Electric shop is called after work is completed and prior to 3:00 PM to reactivate alarm system and notify CCOM 911 that the fire alarm system is back in service.
5-11.6 Continual outage of Fire Alarm system over night or several days shall require an Outage Planning Sheet to be circulated, notification to CCOM 911 requesting building surveillance by University Police Department, notification to the Building's Building Coordinator.
HOT WORK CUTTING, WELDING, and HEAT SOURCE
Hot Work Permit form.
Permit For Hot Work with Portable Equipment
Date______________ Building ____________
Dept.____________ Room and Floor ____________
Time ___________
Description of Work to be done _____________________________________________________
_____________________________________________________
____________________________________________________
Special precautions ______________________________________________
The location where this work is to be done has been examined, the pre-work checklist was reviewed and necessary precautions taken, and permission is granted for this work.
Permit expires ____________________________


Work area and all adjacent areas to which sparks and heat might have spread (Including floors above and below and on opposite side of wall(s) were inspected 30 minutes after the work was completed and were found fire safe. FPM has been notified to reactivate the fire alarm system in the area.
- ____If a fire occurs the fire watcher shall call CCOM 911 for reporting the fire and starting evacuating the building
- ____Call Electrical Shop and Work Control to Turn Fire Alarm System back on and release the building.
______________________________
(Name of Repairperson)
____________________
(Name of Fire Watcher)
Pre Hot Work ---Check list
Attention
Before approving any Hot Work permit, the Repair Department' repairperson shall inspect the work area and confirm that precautions have been taken to prevent fire in accordance with NFPA 51 B.
____Call Work Control to notify Building Coordinator
____Call Electrical Shop to disable Fire Alarm System
Precautions
____Cutting and welding equipment in good repair.
____Portable fire extinguisher must be located such that it is immediately available.
Within 35 feet of work
____Floors swept clean of combustibles
____Fire resistant shields (fire retardant plywood, flameproof tarpaulin, metal, etc.) must cover combustible floors and materials.
____No combustible materials or flammable liquids
____All wall and floor openings covered
Work on walls or ceilings and roof
____Combustibles moved away from opposite side of wall
Work on enclosed equipment
(tanks, containers, ducts, dust collectors, etc.)
- ____Need to meet Confined Space requirements
- ____Equipment cleaned of all combustibles
- ____Containers purged of flammable vapors
Fire Watch
- ____Call for Fire Watch personnel to be provided
- ____To be provided during and 30 minutes after operation
- ____Trained in used of fire extinguisher equipment
- ____Call 911
- ____ Start evacuating the building
Each checkpoint must be initialed by repairperson.

Move on to Chapter 6 Emergency
Medical Care or back to Safety
Manual
|